ERMS 6kVA UPS, Scalable to 36kVA, 400V

ERMS 6kVA UPS, Scalable to 36kVA, 400V
ERMS 6kVA UPS, Scalable to 36kVA, 400V
ERMS 6kVA UPS, Scalable to 36kVA, 400V

The ERMS series UPS system is composed of a monitoring module and multiple 6kVA power modules. This is a type of rack-mounted UPS and could be embedded into a standard 19 inch cabinet or working individual for decentralized power supplying. Sicon provides 3 power module models: ERMS-12/6, ERMS-24/6 and ERMS-36/6, and their maximum power capacities are 12kVA, 24kVA and 36kVA.

ERMS-12/6 UPS System
  • Maximum power: 12kVA
  • Could be embedded into standard 19 inch cabinet
  • Power module model: ERM-06
  • Module power: 6kVA
  • Weight: Approximate 12kg+2*7kg (each module)
  • Dimension: 480*600*132 mm (W*D*H)
  • Weight: 12kg
ERMS-24/6 UPS System
  • Maximum power: 24kVA
  • Could be embedded into standard 19 inch cabinet
  • Power module model: ERM-06
  • Module power: 6kVA
  • Weight: Approximate 16kg+4*7kg (each module)
  • Dimension: 480*600*220 mm (W*D*H)
  • Weight: 16kg
ERMS-36/6 UPS System
  • Maximum power: 36kVA
  • Could be embedded into standard 19 inch cabinet
  • Power module model: ERM-06
  • Module power: 6kVA
  • Weight: Approximate 20kg+6*7kg (each module)
  • Dimension: 480*600*310 mm (W*D*H)
  • Weight: 20kg
UPS System Technical Parameters
Module
Module model ERM-06
Module power 6kVA
Input/output 1/1 phase
Module dimension (W×D×H)mm 220×500×85
Weight (kg) Approximate 7kg
Module charging Each module provides 1A charging current
Input power factor ≥ 0.99
Overload ability Exceeds system overload requirements
Maximum heat dissipation power 340W
THDI (%) ≤ 3%
Mains Input
Input mode 3-phase +N +E, 1-phase +N +E
Input voltage 380V/220V±20%, 400V/230V±20%, 415V/240V±20%
Input frequency 50Hz±10%, 60Hz±10%
Power woke-in (Sec.) 60sec
THDI (%) <3%
Input PF ≥0.99
Bypass Input
Input voltage 380V/220V±20%, 400V/230V±20%, 415V/240V±20%
Input frequency 50 Hz, 60 Hz
Range of Frequency Synchro 50 Hz±4%, 60 Hz±4%
DC Input
Rated Input voltage ±240VDC
Input voltage tolerance ±216V~±246V DC
Battery charging
Charging current limited yes
Charging ability 10 hours (2 hours back up)
Stability of charging voltage ±1%
AC output
UPS power factor 0.9
Output voltage 380V/220V AC, 400V/230V AC, 415V/240V AC
Output frequency ±4%;±0.2% (battery supply)
Output voltage stability ±1%
Output voltage recovering time <20ms (load 0~100% change)
Overload ability Operate 10mins with 125% load
Transfer from mains to battery supply 0ms
Transfer from bypass to inverter supply < 1ms
Peak factor 3:1
Waveform distortion ≤1% ( linear load ), ≤3%( non-linear load )
Overall efficiency ≥95% (AC~AC), ≥98% (DC~AC)
Load share precision ≤5%
Operation environment
Ambient temperature -25℃~60℃
Operating temperature -5℃~40℃
Maximum operation altitude ≤1500m
Relative humidity ≤95% non-cadency
Protection degree IP30
Cooling Air cooling
Applicable safety standards EN62040-1-1:2003 IEC60950-1:2001
Electromagnetic compatibility EN62040-2:2006
Acoustic noise ≤55DB
Others
Cabinet Standard 19 inch cabinet
Monitor management system UPSupervisor
Interface RS232, RS485, 2 try contact, TCP/IP adapter
Display LCD/LED